1MRS756378 D
REF615
Application Manual
There are four IED variant specific setting groups. Parameters can be set
independently for each setting group.
The active setting group (1...4) can be changed with a parameter. The change of an
active setting group can also be made via a binary input if the binary input is enabled
for this. To enable the change of an active setting group via a binary input, connect
a free binary input with SMT to the ActSG input of the SGCB-block.
Table 12:
Binary input states and corresponding active setting groups
BI State
OFF
ON
The active setting group defined by a parameter is overridden when a binary input is
enabled for changing the active setting group.
DIRECTIONAL OR INTERMITTENT EARTH FAULT PROTECTION
X110
3
BI 2 (BACTRL)
4
DOUBLE (CROSS COUNTRY) EARTH FAULT PROTECTION
A071334 V4 EN
Figure 18:
Directional earth-fault protection
Active setting group
1
2
DEFLPDEF1
I > (1)
0
67N-1 (1)
I0
START
U0
OPERATE
BLOCK
ENA_MULT
RCA_CTL
DEFLPDEF2
I > (2)
0
67N-1 (2)
I0
START
U0
OPERATE
BLOCK
ENA_MULT
RCA_CTL
LED2 (DEF OPERATE)
OR
DEFHPDEF
I >>
0
67N-2
I0
START
U0
OPERATE
BLOCK
ENA_MULT
RCA_CTL
INTRPTEF1
I >
0
67NIEF
I0
START
U0
OPERATE
BLOCK
BLK_EF
EFHPTOC1
I >>
0
51N-2
I0
START
LED3 (NEF OPERATE)
BLOCK
OPERATE
ENA_MULTI
Calculated Io
Section 3
REF615 variants
49