Start of any protection function SO1 (X100:10-12)
Operation (trip) of any protection function SO2 (X100:13-14)
Operation (trip) of any stage of the overcurrent protection function SO2
(X110:17-19)
Operation (trip) of any stage of the earth-fault protection function SO3
(X110:20-22)
The two TPGAPC blocks 1 and 2 are timers and used for setting the minimum pulse
length for the outputs. There are four generic timers (TPGAPC1..4) available in the
IED. The remaining ones not described in the functional diagram are available in
SMT for connection where applicable.
Standard configuration F including directional
overcurrent protection with voltage protection
Applications
The standard configuration for directional overcurrent protection is mainly intended
for cable and overhead line feeder applications in isolated and resonant-earthed
distribution networks, where directional protections are necessary to improve the
selectivity of the fault detection. The standard configuration includes phase voltage
and residual voltage protection and measurement and also power and energy
measurement.
The IED with this standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and internal
signal designation within the IED enables this configuration to be further adapted to
different primary circuit layouts and the related functionality needs by modifying the
internal functionality with SMT and PST.
Functions
Table 20:
Functions included in the REF615 standard configuration including directional
overcurrent protection with voltage protection
Function
Three-phase directional overcurrent protection,
low stage, instance 1
Three-phase directional overcurrent protection,
low stage, instance 2
Three-phase directional overcurrent protection,
high stage
Three-phase non-directional overcurrent
protection, instantaneous stage
Arc protection
Table continues on next page
REF615 variants
IEC 61850
IEC
DPHLPDOC1
3I> → (1)
DPHLPDOC2
3I> → (2)
DPHHPDOC1
3I>> →
PHIPTOC1
3I>>>
ARCSARC1
ARC (1)
ARCSARC2
ARC (2)
ARCSARC3
ARC (3)
Section 3
ANSI
67-1 (1)
67-1 (2)
67-2
50P/51P
50L/50NL (1)
50L/50NL (2)
50L/50NL (3)
93