ABB REF615 Applications Manual page 143

Feeder protection and control
Hide thumbs Also See for REF615:
Table of Contents

Advertisement

1MRS756378 D
REF615
Application Manual
A070980 V1 EN
Figure 63:
Numerical overcurrent protection functionality for a typical sub-
transmission/distribution substation (feeder protection not shown).
Blocking output = digital output signal from the start of a protection
stage, Blocking in = digital input signal to block the operation of a
protection stage
The operating times of the time selective stages are very short, because the grading
margins between successive protection stages can be kept short. This is mainly due
to the advanced measuring principle allowing a certain degree of CT saturation, good
operating accuracy and short retardation times of the numerical units. So, for example,
a grading margin of 150 ms in the DT mode of operation can be used, provided that
the circuit breaker interrupting time is shorter than 60 ms.
The sensitivity and speed of the current-selective stages become as good as possible
due to the fact that the transient overreach is practically zero. Also, the effects of
switching inrush currents on the setting values can be reduced by using the IED logic,
which recognizes the transformer energizing inrush current and blocks the operation
or multiplies the current start value setting of the selected overcurrent stage with a
predefined multiplier setting.
Finally, a dependable trip of the overcurrent protection is secured by both a proper
selection of the settings and an adequate ability of the measuring transformers to
reproduce the fault current. This is important in order to maintain selectivity and also
for the protection to operate without additional time delays. For additional
information about available measuring modes and current transformer requirements,
refer to section where general function block features are described in the IED
technical manual.
Section 5
Protection functions
137

Advertisement

Table of Contents
loading

Table of Contents