ABB REF615 Applications Manual page 89

Feeder protection and control
Hide thumbs Also See for REF615:
Table of Contents

Advertisement

1MRS756378 D
REF615
Application Manual
Four overcurrent stages are available for overcurrent and short-circuit protection. The
instantaneous stage (PHIPTOC1) can be blocked by energizing the binary input 1
(X120:1-2). Two negative-sequence overcurrent stages (NSPTOC1 and NSPTOC2)
are available for phase unbalance protection. The inrush detection block's
(INRPHAR1) output BLK2H enables either blocking the function or multiplying the
active settings for any of the shown protection function blocks.
GUID-37D627C4-6097-4322-BACC-161CC6039EC5 V1 EN
Figure 41:
Overcurrent protection and inrush indication
All operate signals are connected to the Master Trip and also to the alarm LEDs.
LED1 is used for overcurrent and LED 4 for negative sequence overcurrent protection
operate indication. LED 4 is also used for phase discontinuity protection operate
indication.
The upstream blocking from the start of the overcurrent second high stage
(PHHPTOC2) is connected to the output SO1 (X110:14-16). This output is used for
sending a blocking signal to the relevant overcurrent protection stage of the IED at
the infeeding bay.
There are four IED variant specific setting groups. Parameters can be set
independently for each setting group.
The active setting group (1...4) can be changed with a parameter or via a binary input
if the binary input is enabled for this. To enable the change of an active setting group
Section 3
REF615 variants
83