1MRS756378 D
REF615
Application Manual
A071114 V2 EN
Figure 103:
Trip Curves for a typical 12 kV, 630 A, 16 kA vacuum interrupter
Nr =
the number of closing-opening operations allowed for the circuit breaker
Ia =
the current at the time of tripping of the circuit breaker
Calculation of Directional Coef
The directional coefficient is calculated according to the formula:
B
log
A
=
= −
DirectionalCoef
I
f
log
I
r
A070794 V1 EN
I
Rated operating current = 630 A
r
I
Rated fault current = 16 kA
f
A
Op number rated = 30000
B
Op number fault = 20
Calculation for estimating the remaining life
Condition monitoring functions
. 2 2609
Section 8
(Equation 12)
203