ABB REF615 Applications Manual page 50

Feeder protection and control
Hide thumbs Also See for REF615:
Table of Contents

Advertisement

Section 3
REF615 variants
44
A071328 V3 EN
Figure 15:
Circuit breaker control
The ENA_CLOSE input, that is, enable the closing of the circuit breaker, in the
breaker control function block CBXCBR is a combination of the status of the Master
Trip. The open operation is always enabled.
If the ENA_CLOSE signal is completely removed from the breaker
control function block CBXCBR with SMT, the function assumes
that the breaker close commands are allowed continuously.
A071330 V3 EN
Figure 16:
Alarm indication
The signal outputs from the IED are connected to give dedicated information on:
start of any protection function SO1 (X100:10-12)
operation (trip) of any protection function SO2 (X100:13-15).
1MRS756378 D
REF615
Application Manual