ABB REF615 Applications Manual page 106

Feeder protection and control
Hide thumbs Also See for REF615:
Table of Contents

Advertisement

Section 3
REF615 variants
100
GUID-EC907A8E-9CF0-4150-A394-FFBAF30A8725 V1 EN
Figure 53:
Arc protection
The ARC protection offers individual function blocks for three ARC sensors that can
be connected to the IED. Each ARC protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the ARC protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.
The autorrecloser is configured to be initiated by operate signals from a number of
protection stages through the INIT1-5 inputs. It is possible to create individual
autorreclose sequences for each input.
The autorreclose function can be blocked with the INHIBIT_RECL input. As a
default, the operation of some selected protection functions are connected to this
1MRS756378 D
REF615
Application Manual