Section 3
RED615 standard configurations
3.4.3.3
36
GUID-E87263FE-32FF-415C-89F0-AEFC537D076C V1 EN
Figure 16:
Trip circuit supervision
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked
by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open
signal. The TCS alarm indication is connected to LED 9.
By default it is expected that there is no external resistor in the
circuit breaker tripping coil circuit connected parallel with circuit
breaker normally open auxiliary contact.

Functional diagrams for control and interlocking

GUID-DA0317C8-79B8-4892-9BBD-C05240236D08 V1 EN
Figure 17:
Master Trip
The operate signals from the protections are connected to the two trip output
contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master
Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker
from local or remote CBXCBR1-exe_op is connected directly to the output PO3
(X100:15-19).
1MRS756498 D
RED615
Application Manual