General Parameters - ABB REF615 Applications Manual

Feeder protection and control
Hide thumbs Also See for REF615:
Table of Contents

Advertisement

1MRS756378 D
Section 4
4.1
Table 23:
Analog channel settings, phase currents
Parameter
Values (Range)
Secondary current
1=0.2A
2=1A
3=5A
Primary current
1.0...6000.0
Amplitude corr. A
0.900...1.100
Amplitude corr. B
0.900...1.100
Amplitude corr. C
0.900...1.100
Table 24:
Analog channel settings, residual current
Parameter
Values (Range)
Secondary current
1=0.2A
2=1A
3=5A
Primary current
1.0...6000.0
Amplitude corr.
0.900...1.100
Table 25:
Analog channel settings, phase voltages
Parameter
Values (Range)
Primary voltage
0.001...440.000
Secondary voltage
1=100V
2=110V
3=115V
4=120V
VT connection
1=Wye
2=Delta
Table continues on next page
REF615
Application Manual
Basic functions

General parameters

Unit
A
Unit
A
Unit
kV
Step
Default
2=1A
0.1
100.0
0.001
1.000
0.001
1.000
0.001
1.000
Step
Default
2=1A
0.1
100.0
0.001
1.000
Step
Default
0.001
20.000
1=100V
2=Delta
Section 4
Basic functions
Description
Rated secondary
current
Rated primary
current
Phase A amplitude
correction factor
Phase B amplitude
correction factor
Phase C amplitude
correction factor
Description
Secondary current
Primary current
Amplitude correction
Description
Primary rated
voltage
Secondary rated
voltage
Wye or delta VT
connection
111

Advertisement