Functional Diagrams For Control - ABB REF611 Applications Manual

Relion 611 series feeder protection and control
Hide thumbs Also See for REF611:
Table of Contents

Advertisement

1MRS757456 D
3.4.3.3
REF611
Application Manual

Functional diagrams for control

OSWGAPC1
IN_1
PHLPTOC1_OPERATE
IN_2
PHHPTOC1_OPERATE
IN_3
PHHPTOC2_OPERATE
IN_4
PHIPTOC1_OPERATE
IN_5
EFHPTOC1_OPETATE
IN_6
DEFLPDEF1_OPERATE
IN_7
DEFLPDEF2_OPERATE
IN_8
DEFHPDEF1_OPERATE
IN_9
ROVPTOV1_OPERTAE
IN_10
ROVPTOV2_OPERTAE
IN_11
ROVPTOV3_OPERTAE
IN_12
INTRPTEF1_OPERATE
IN_13
NSPTOC1_OPERATE
IN_14
NSPTOC2_OPERATE
IN_15
PDNSPTOC1_OPERATE
MVGAPC1
SELGAPC1_External Trip
IN1
GOOSERCV_BIN 2_OUT
IN2
OR
GOOSERCV_BIN 3_OUT
SELGAPC1_RST_LKOUT
CBXCBR1_EXE_OP
DARREC1_OPEN_CB
IN_1
PHLPTOC1_OPERATE
IN_2
PHHPTOC1_OPERATE
IN_3
PHHPTOC2_OPERATE
IN_4
PHIPTOC1_OPERATE
IN_5
EFHPTOC1_OPETATE
IN_6
DEFLPDEF1_OPERATE
IN_7
DEFLPDEF2_OPERATE
IN_8
DEFHPDEF1_OPERATE
IN_9
ROVPTOV1_OPERTAE
IN_10
ROVPTOV2_OPERTAE
IN_11
ROVPTOV3_OPERTAE
IN_12
INTRPTEF1_OPERATE
IN_13
NSPTOC1_OPERATE
IN_14
NSPTOC2_OPERATE
IN_15
PDNSPTOC1_OPERATE
IN_17
CCBRBRF1_TRRET
SELGAPC1_External Trip
GOOSERCV_BIN 2_OUT
OR
GOOSERCV_BIN 3_OUT
SELGAPC1_RST_LKOUT
GUID-A4419861-FA17-4E12-8951-ABEB715AA740 V2 EN
Figure 24:
Master trip
The operate signals from the protections and an external trip are connected to the two
trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding
Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit
breaker from local or remote CBXCBR1_EXE_OP or from the autoreclosing
REF611 standardized configurations
MASTER TRIP #1
TRPPTRC1
OUT
OR
BLOCK
OR
OPERATE
CL_LKOUT
RST_LKOUT
Q1
Q2
MASTER TRIP #2
OSWGAPC2
TRPPTRC2
OUT
OR
BLOCK
OR
OPERATE
RST_LKOUT
MVGAPC1
IN1
Q1
IN2
Q2
Section 3
SELGAPC3
TRIP
IN_1
OUT_5
OR
SELGAPC3
OUT_6
IN_2
TRIP
CL_LKOUT
X100 PO3
X100 PO4
47