Current Circuit Supervision Ccrdif - ABB REF615 Applications Manual

Feeder protection and control
Hide thumbs Also See for REF615:
Table of Contents

Advertisement

Section 7
Supervision functions
7.2
7.2.1
7.2.2
194
A070974 V3 EN
Figure 97:
Incorrect testing of IEDs

Current circuit supervision CCRDIF

Identification
Table 79:
Function identification
IEC 61850 identification:
IEC 60617 identification:
ANSI/IEEE C37.2 device number:
Functionality
The current circuit supervision function CCRDIF is used for monitoring current
transformer secondary circuits.
CCRDIF calculates internally the sum of phase currents (I_A, I_B and I_C) and
compares the sum against the measured single reference current (I_REF). The
reference current must originate from other three phase CT cores than the phase
CCRDIF
MCS 3I
MCS 3I
1MRS756378 D
REF615
Application Manual