M6 bolt
Affinity User Guide
Issue Number: 5
Electrical
Getting
Basic
Installation
Started
parameters
Plain washers
Spring washer
www.controltechniques.com
Running
SMARTCARD
Optimization
the motor
operation
Figure 4-7 Size 4, 5 and 6 ground connections
The ground loop impedance must conform to the
requirements of local safety regulations.
The drive must be grounded by a connection capable of
carrying the prospective fault current until the protective
WARNING
device (fuse, etc.) disconnects the AC supply.
The ground connections must be inspected and tested at
appropriate intervals.
4.2

AC supply requirements

Voltage:
BAx2xx
200V to 240V ±10%
BAx4xx
380V to 480V ±10%
BAx5xx
500V to 575V ±10%
BAx6xx
500V to 690V ±10%
Number of phases: 3
Maximum supply imbalance: 2% negative phase sequence (equivalent
to 3% voltage imbalance between phases).
Frequency range: 48 to 65 Hz
For UL compliance only, the maximum supply symmetrical fault current
must be limited to 100kA
4.2.1
Supply types
All drives are suitable for use on any supply type i.e TN-S, TN-C-S, TT
and IT.
Supplies with voltage up to 600V may have grounding at any
potential, i.e. neutral, centre or corner ("grounded delta")
Supplies with voltage above 600V may not have corner grounding
Drives are suitable for use on supplies of installation category III and
lower, according to IEC60664-1. This means they may be connected
permanently to the supply at its origin in a building, but for outdoor
installation additional over-voltage suppression (transient voltage surge
suppression) must be provided to reduce category IV to category III.