17.39
Response turn-around time
RW
Uni
0 to 255 ms
Modbus RTU only
There will always be a finite delay between the end of a message from
the host (master) and the time at which the host is ready to receive the
response from the drive (slave). The drive does not respond until at least
1ms after the message has been received from the host allowing 1ms for
the host to change from transmit to receive mode. This initial delay can
be extended using Pr 17.39 if required.
Pr 17.39
The transmitters are turned on and data transmission
0
begins immediately after the initial delay (≥1ms).
The transmitters are turned on after the initial delay
1
(≥1ms) and data transmission begins 1ms later.
The transmitters are turned on after a delay of at least the
2 or more
time specified in Pr 17.39 and data transmission begins
1ms later.
Modbus RTU uses a silent period detection system to detect the end of a
message. This silent period is either the length of time for 3.5 characters
at the present baud rate or the length of time set in Pr 17.39 whichever is
the longest.
17.44
Real-time clock battery low
RO
Uni
0 to 255
The real-time clock backup battery is checked upon power up and after a
drive reset to determine if it should be changed. The conditions requiring
battery replacement are when all power has been lost to the real-time
clock while the drive was un-powered or that the battery voltage has
fallen below 2.5Vdc.
If this parameter is 1 then the real-time clock backup battery should be
replaced at the earliest opportunity.
The real-time clock will continue to operate as long as the drive remains
powered.
For instructions of how to replace the battery of the real-time clock, refer
to Figure 3-63 on page 65.
17.45
Communications OK flag
RO
Uni
0 to 255
This parameter has a value of 1 when the building automation network
communications are OK and zero when the communications lost
detection determines that an error has occurred; this is determined
differently for BACnet and MetaSys as follows: -
BACnet
The network is monitored for the presence of an active token; should this
token disappear for the time specified in parameter Pr 17.12 the drive
will take the action configured in parameter Pr 17.13.
MetaSys
The network is monitored for any message. Receipt of a valid message
(regardless of intended destination) will be seen as communications
being OK. If no valid message is received within time specified in
Pr 17.12 the drive will take the action configured in parameter Pr 17.13.
It is important to ensure that a message is placed onto the network
within the configured time-out period to prevent spurious drive operation.
Affinity User Guide
Issue Number: 5
Electrical
Getting
Basic
Running
Installation
Started
parameters
the motor
US
5
Action
NC
PT
NC
www.controltechniques.com
SMARTCARD
Optimization
PC tools
operation
17.50
Error status
RO
Uni
0 to 255
If the Solutions Module detects a fault then the drive will trip with an
SL3.Er trip. The source of the trip can then be discovered from the error
code written into Pr 17.50.
Possible error codes are shown in the table below:
Pr 17.50
0
No error
10
Solutions Module operating system error
20
Real-time clock error
30
IP54 cooling fan power supply fault
40
Drive to Solutions Module interface error
50
Building automation network error
74
Solutions Module PCB over-temperature
Advanced
Technical
Diagnostics
parameters