1.7 In-line gage transmitter orientation
The low side pressure port (atmospheric reference) on the in-line gage
transmitter is located under the sensor module neck label. (See
Keep the vent path free of any obstruction, including but not limited to paint,
dust, and lubrication by mounting the transmitter so any contaminants can drain
away.
Figure 3. In-line Gage Transmitter
A. Low side pressure port (under neck label)

2.0 Consider housing rotation

To improve field access to wiring or to better view the optional LCD display:
1. Loosen the housing rotation set screw.
2. First rotate the housing clockwise to the desired location. If the desired
location cannot be achieved due to thread limit, rotate the housing counter
clockwise to the desired location (up to 360° from thread limit).
3. Retighten the housing rotation set screw up to 30 in-lb.
Figure 4. Transmitter Housing Set Screw