10.2 System parameter list for levels 1 to 3

r0000
VSD display
Displays the user selected output as defined in P0005
Unit: -
Min: -
Note:
Pressing the "Fn" button for 2 seconds allows the user to view the values of DC link voltage, output current, output volt-
age, and chosen r0000 setting (defined in P0005)
r0002
VSD state
Displays actual VSD state
Unit: -
Min: -
Settings:
0=Commissioning mode (P0010=0)
1=VSD ready
2=VSD fault active
Dependency:
State 3 visible only while precharging DC link and when externally powered communications board is fitted
P0003
User access level
Defines user access level to parameter sets. The default setting (standard) is sufficient for most
simple applications
Unit: --
Min: 0
Settings:
0=User-defined parameter list - see P0013 for details
1=Standard: Access into frequently used parameters
2=Extended: Access to e.g. VSD I/O functions.
P0004
Parameter filter
Filters available parameters according to functionality to enable a more focussed approach to
Commissioning
Unit: -
Min: 0
Example:
P0004=22 specifies that only PID parameters will be visible
Settings:
0=All parameters
2=VSD
3=Motor
4=Speed sensor
Dependency:
Parameters marked "Quick Comm: Yes" in the parameter header can only be set when P0010=1 (quick commissioning)
Note:
The VSD will start with any setting of P0004
P0005
Display selection
Selects display for parameter r0000 (VSD display)
Unit: -
Min: 2
Settings:
21=Actual frequency
Note:
These settings refer to read only parameter numbers ("rxxxx")
Details:
See relevant "rxxxx" parameter descriptions
P0006
Display mode
Defines mode of display for r0000 (VSD display)
Unit: -
Min: 0
Settings: 0=In Ready state alternate between setpoint and output fre-
quency. During run, display output frequency
1=In Ready state display setpoint. In run display output freq.
2=In Ready state alternate between P0005 value and r0020
value. In run display P0005 value
Note:
When VSD is not running, the display alternates between the values for "Not Running" and "Running".
Per default, the setpoint and actual frequency values are displayed alternately
P0010
Commissioning parameter filter
Filters parameters so that only those related to a particular functional group are selected
Unit: -
Min: 0
Settings:
0=Ready
1=Quick commissioning
2=VSD
Dependency:
Reset to 0 for VSD to run
P0003 (user access level) also determines access to parameters
Note:
If P3900 is not 0 (0 is the default value), this parameter is automatically reset to 0
P0011
Lock for user-defined parameter
Unit: -
Min: 0
Details:
See P0013 (user-defined parameter)
P0012
Key for user-defined parameter
Unit: -
Min: 0
Details:
See P0013 (user-defined parameter).
P0013[20]
User-defined parameter
Defines a limited set of parameters to which the enduser will have access
Unit: -
Min: 0
Siemens Building Technologies
HVAC Products
Def: -
Def: -
3=VSD starting (DC link precharging)
4=VSD running
5=Stopping (ramping down)
Def: 1
Def: 0
5=Techn. application / units
7=Commands, binary I/O
8=ADC and DAC
10=Setpoint channel / RFG
Def: 21
25=Output voltage
Def: 2
Def: 0
Def: 0
Def: 0
Def: 0
Commissioning Guide
10 Parameterization
Max: -
Max: -
Max: 4
3=Expert: For experienced users only
4=Service: Only for use by authorized service staff
Max: 22
12=VSD features
21=Alarms / warnings / monitoring
13=Motor control
22=Controller (e.g. PID)
20=Communication
Max: 2294
26=DC link voltage
Max: 4
3=In Ready state alternate between r0002 value and
r0020 value. In run display r0002 value
4=In all states just display P0005
Max: 30
29 =Download
30 =Factory setting
Max: 65535
Max: 65535
Max: 65535
Level 1
Level 3
Level 1
Level 1
Level 2
27=Output current
Level 3
Level 1
Level 3
Level 3
Level 3
49/80
CM1G5192en
26.02.2003