Siemens sed2 Commissioning Manual page 75

Variable speed drives
Hide thumbs Also See for sed2:
Table of Contents

Advertisement

Note:
When setting 1 is selected, only the parameter settings carried out via the commissioning menu "Quick commissioning"
are retained. All other parameter changes, including the I/O settings, are lost. Motor calculations are also performed.
When setting 2 is selected, only the parameters that depend on the parameters in the commissioning menu "Quick
commissioning" (P0010=1) are calculated. The I/O settings are also reset to default and the motor calculations per-
formed.
When setting 3 is selected, only the motor and controller calculations are performed. Exiting quick commissioning with
this setting saves time (for example, if only motor rating plate data have been changed).
Calculates a variety of motor parameters, overwriting previous values. These include P0344 (level 3, motor weight),
P0350 (level 3, demagnetization time), P2000 (reference frequency), P2002 (level 3, reference current).
Siemens Building Technologies
HVAC Products
Commissioning Guide
10 Parameterization
75/80
CM1G5192en
26.02.2003

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents