Note:
When setting 1 is selected, only the parameter settings carried out via the commissioning menu "Quick commissioning"
are retained. All other parameter changes, including the I/O settings, are lost. Motor calculations are also performed.
When setting 2 is selected, only the parameters that depend on the parameters in the commissioning menu "Quick
commissioning" (P0010=1) are calculated. The I/O settings are also reset to default and the motor calculations per-
formed.
When setting 3 is selected, only the motor and controller calculations are performed. Exiting quick commissioning with
this setting saves time (for example, if only motor rating plate data have been changed).
Calculates a variety of motor parameters, overwriting previous values. These include P0344 (level 3, motor weight),
P0350 (level 3, demagnetization time), P2000 (reference frequency), P2002 (level 3, reference current).