Siemens sed2 Commissioning Manual page 54

Variable speed drives
Hide thumbs Also See for sed2:
Table of Contents

Advertisement

Note:
100% means: Z rated motor =
P0400
Select encoder type
Selects encoder type
Unit: -
Min: 0
Settings:
0=disabled
1=Single channel encoder
2=Quadrature encoder without zero pulse
Note:
The term "quadrature" in settings 2 and 12 refers to 2 periodic functions separated by a quarter cycle or 90 degrees
P0409
Pulses per second at rated frequency
Sets number of pulses per second at rated speed
Unit: -
Min: 1
P0501[2]
Type of sensor
Defines type of process variable sensor that each analog input is to be configured for. Note
that setting this parameter will in turn set P0756 (analog input mode). To switch between volt-
age and current analog input modes also requires the DIP switches on the terminal board to be
set correctly. See description for P0756. See P0753 and P0756 to P0762 (ADC conditioning)
Unit: -
Min: 0
Settings:
0=No sensor selected
1=Sensor type QBE620 P1
2=Sensor type QBE620 P10
3=Sensor type QBE620 P16
4=Sensor type QBE620 P25
5=Sensor type QBE620 P40
6=Sensor type QBE620 P4
7=Sensor type QBE620 P5
8=Sensor type QBE621 P10U
9=Sensor type QBE621 P25U
Details:
P0501(Index 0): VSD in Auto mode
P0501(Index I): VSD in Hand mode
P0506[10]
Parameter list
This parameter performs no function within the VSD. It is a storage place for use with the AOP
for a list of parameters to scale
Unit: -
Min: 0
Index:
P0506[0]: Parameter 1
P0506[1]: Parameter 2
P0506[2]: Parameter 3
P0507[3]
Scalar values
This parameter performs no function within the VSD. It is a storage place for use with the AOP
to scale particular parameters
Unit: -
Min: 0
Index:
P0507[0]: Scalar numerator
P0508[4]
Unit
This parameter performs no function within the VSD. It is a storage place for use with the AOP
to store a string for unit
Unit: -
Min: 0
Index:
P0508[0]: Unit character 1
P0509[12]
String
This parameter performs no function within the VSD. It is a storage place for use with the AOP
to store a string for parameter unit description
Unit: -
Min: 0
Index:
P0509[0]: String char 1
P0509[1]: String char 2
P0509[2]: String char 3
P0601
Motor temperature sensor
Selects motor temperature sensor
Unit: -
Min: 0
Settings:
0=No sensor
Dependency:
If "no sensor" is selected, motor temperature monitoring occurs based on the estimated value of the thermal motor
model
P0610
Motor I2t temperature reaction
Defines reaction when motor temperature reaches warning threshold
Unit: -
Min: 0
Settings:
0=No reaction, warning only
P0640
Motor overload factor [%]
Defines reaction when motor temperature reaches warning threshold
Unit: %
Min: 10.0
Dependency:
Limited to maximum VSD current or to 400 % of rated motor current (P0305), whichever is lower
54/80
Siemens Building Technologies
HVAC Products
P0304 (rated motor voltage)
P0305 (rated motor current)
Def: 0
Def: 25
Def: 0
10=Sensor type QBE63 DP01
11=Sensor type QBE63 DP02
12=Sensor type QBE63 DP05
13=Sensor type QBE63 DP1
14=Sensor type QBE64 DP4
15=Sensor type 0 TO 1 INCH WC
16=Sensor type 0 TO 2 INCH WC
17=Sensor type 0 TO 2.5 INCH WC
18=Sensor type 0 TO 3 INCH WC
19=Sensor type 0 TO 5 INCH WC
Def: 754
P0506[3]: Parameter 4
P0506[4]: Parameter 5
P0506[5]: Parameter 6
Def: 1.0
P0507[1]: Scalar denominator
Def: 0
P0508[1]: Unit character 2
Def: 0
P0509[3]: String char 4
P0509[4]: String char 5
P0509[5]: String char 6
Def: 0
1=PTC thermistor
Def: 2
1=Warning and Imax reduction (results in reduced output freq.)
Def: 110.0
Commissioning Guide
10 Parameterization
Max: 12
3=External pulse train
12=Quadrature encoder with zero pulse
Max: 500
Max: 51
20=Sensor type 0 TO 10 INCH WC
21=Sensor type 0 TO 10 PSI
22=Sensor type 0 TO 15 PSI
23=Sensor type 0 TO 25 PSI
24=Sensor type 0 TO 30 PSI
25=Sensor type 0 TO 50 PSI
26=Sensor type 0 TO 60 PSI
27=Sensor type 0 TO 100 PSI
28=Sensor type 0 TO 150 PSI
29=Sensor type LG-Ni 1000: -50 to 150 °C
Max: 4000
P0506[6]: Parameter 7
P0506[7]: Parameter 8
P0506[8]: Parameter 9
Max: 9999.9
P0507[2]: Scalar offset
Max: 65535
P0508[2]: Unit character 3
Max: 65535
P0509[6]: String char 7
P0509[7]: String char 8
P0509[8]: String char 9
Max: 2
2=KTY84
Max: 2
Max: 400.0
Level 3
Level 3
Level 2
Level 3
P0506[9]: Parameter 10
Level 3
Level 3
P0508[3]: Unit character 4
Level 3
P0509[9]: String char 10
P0509[10]: String char 11
P0509[11]: String char 12
Level 3
Level 3
2=Warning and trip
Level 3
CM1G5192en