Advertisement

Par. no.
Value Parameter function
P2200
1
Enable PID controller
P2201
60
Fixed PID setpoint
P2253
2224
PID setpoint
P2264
755.0
PID feedback
P2274
0
PID derivative action time
P2280
1.5
PID proportional band
P2285
20
PID integral action time
P2306
0
PID acting direction
P2390
20
Hibernation frequency
P2391
60
Hibernation timer
P2392
-5
Restart PID controller deviation
r2262
60
Filtered PID setpoint
r2272
64
PID scaled feedback
r2273
-1.2
PID error
r2294
70
PID output
8

Additional functions

8.1 Belt failure detection without sensor

Carry out quick commissioning and modify the parameters for normal operation, then proceed as follows:
Frequency /
torque curve

8.1.1 Parameter setting

Start with quick commissioning according to application example 1
Par. no.
Value
Parameter function
P0003
3
User access level
P2181
6
Belt failure detection mode Trip on high / low torque / speed
P2182
14 Hz
Belt threshold 1
40/80
Siemens Building Technologies
HVAC Products
Torque [Nm]
P2189
Upper torque threshold 3
P2190 unterer
Lower torque threshold 3
P2187
Upper torque threshold 2
P2188
Lower torque threshold 2
P2185
Upper torque threshold 1
P2186
Lower torque threshold 1
Threshold frequency 1
Function selection
Expert access
Sets a frequency threshold F1 for comparing actual torque to
torque the envelope for belt failure detection. The frequency
torque envelope is defined by 9 parameters - 3 are frequency
parameters (P2182 - P2184) and the other 6 define the low
and high torque limits (P2185 - P2190) for each frequency
Commissioning Guide
8 Additional functions
Function selection
Enable PID loop
Fixed setpoint as a percentage of sensor range
PID setpoint source
Sets PID feedback source to AI-1
Derivative action time
Proportional band
Integral action time
Direct acting loop
Hibernation setpoint [%]
Hibernation timer in seconds
Restart – PID error in %
Display actual setpoint in C
Display actual condenser temperature
Display actual PID error in %
Display actual VSD output in %
P2183
P2182
Threshold frequency 2
Threshold frequency 3
Frequency [Hz]
P2184
CM1G5192en
26.02.2003