Siemens sed2 Commissioning Manual page 68

Variable speed drives
Hide thumbs Also See for sed2:
Table of Contents

Advertisement

P2100[3]
Alarm number selection
Selects up to 3 faults or warnings for non-default reactions
Unit: -
Min: 0
Example:
If you want F0005 to perform an OFF3 instead of an OFF2, set P2100[0]=5, then select the desired response in
P2101[0] (in this case, set P2101[0]=3)
Note:
All fault codes have a default response to OFF2. Some fault codes caused by hardware trips (e.g. overcurrent) cannot
be changed from the default responses
P2101[3]
Stop reaction value
Sets VSD stop reaction values for fault selected by P2100 (alarm number stop reaction).
This indexed parameter specifies the special response to the faults / warnings defined in
P2100 indices 0 to 2
Unit: -
Min: 0
Settings:
0=No reaction, no display
1=OFF1 stop reaction
Note:
Settings 0 - 3 are only available for fault codes
Settings 0 and 4 are only available for warnings
Index 0 (P2101) refers to fault / warning in index 0 (P2100)
r2110[4]
Warning number
Displays warning information
Unit: -
Min: -
Details
A maximum of 2 active warnings (indices 0 and 1) and 2 historical warnings (indices 2 and 3) may be viewed
Index:
r2110[0]: Recent Warnings --, warning 1
r2110[1]: Recent Warnings --, warning 2
Note:
The keypad will flash while a warning is active. The LEDs indicate the warning status in this case
If an AOP is in use, the display will show number and text of the active warning
Indices 0 and 1 are not stored
P2111
Total number of warnings
Displays number of warning (up to 4) since last reset. Set to 0 to reset the warning history
Unit: -
Min: 0
r2114[2]
Run time counter
Displays run time counter. It is the total time the VSD has been powered up. Every time you do
power cycle, it will save the value; then, restore it and the counter carries on ticking
Unit: -
Min: -
Settings:
r2114[0]: = System time, seconds, upper word
Details:
See r0948 (fault time)
P2115[3]
AOP real time clock
Displays AOP real time
Unit: -
Min: 0
Index:
P2115[0]: real time, seconds+minutes
Details:
See r0948 (fault time)
P2181
Belt failure detection mode
Sets belt failure detection mode.
Unit: -
Min: 0
Details:
This function allows detection of mechanical failure of the drive train, e.g. a broken drive belt. It can also detect condi-
tions which cause an overload, such as a jam.
Settings:
0=Belt failure detection disabled
1=Warn low torque / speed
2=Warn high torque / speed
P2182
Belt threshold frequency 1
Sets a frequency threshold F1 for comparing actual torque to torque the envelope for belt
failure detection
Unit: Hz
Min: 0.00
Details:
The frequency torque envelope is defined by 9 parameters - 3 are frequency parameters (P2182 - P2184), and the other
6 define the low and high torque limits (P2185 - P2190) for each frequency
Note:
The torque is unlimited below P2182, and above P2184. Normally P2182 <= lower torque limit (P1521), and P2184
>=upper torque limit (P1520)
P2183
Belt threshold frequency 2
Sets a threshold F2 for comparing actual torque to torque the envelope for belt failure detection
Unit: Hz
Min: 0.00
Note:
See P2182 (belt threshold frequency 1)
P2184
Belt threshold frequency 3
Sets a threshold F3 for comparing actual torque to torque the envelope for belt failure detection
Unit: Hz
Min: 0.00
Note:
See P2182 (belt threshold frequency 1)
P2185,
Upper torque threshold 1, 2, and 3
P2187, P2189
Upper limit threshold value for comparing the actual torque
Unit: Nm
Min: 0.0
Note:
See P2182 (belt threshold frequency 1)
68/80
Siemens Building Technologies
HVAC Products
Def: 0
Def: 0
2=OFF2 stop reaction
3=OFF3 stop reaction
Def: -
Def: 0
Def: -
Def: 0
P2115[1]: real time, hours+days
Def: 0
3=Warn high / low torque / speed
4=Trip low torque / speed
Def: 5.00
Def: 30.00
Def: 50.00
Def: 99999.0
Commissioning Guide
10 Parameterization
Max: 65535
Max: 5
4=No reaction warning only
5=Goto fixed frequency 15
Max: -
r2110[2]: Recent Warnings -1, warning 3
r2110[3]: Recent Warnings -1, warning 4
Max: 4
Max: -
r2114[1]: = System time, seconds, lower word
Max: 65535
P2115[2]: real time, month+year
Max: 6
5=Trip high torque / speed
6=Trip high / low torque / speed
Max: 650.00
Max: 650.00
Max: 650.00
Max: 99999.0
Level 3
Level 3
Level 3
Level 3
Level 3
Level 3
Level 3
Level 3
Level 3
Level 3
Level 3
CM1G5192en
26.02.2003