P0700[2]
Selection of command source
Selects digital command source
Unit: -
Min: 0
Settings:
0=Factory default setting
1=BOP (keypad)
Index:
P0700[0]: VSD in Auto mode
Note:
Changing this parameter resets (to default) all settings on item selected. For example: Changing form 1 to 2 resets all
digital inputs to default settings
P0701[2]
Function of digital input 1
Selects function of digital input 1
Unit: -
Min: 0
Settings:
0=Digital input disabled
1=ON/OFF1
2=ON reverse /OFF1
3=OFF2 - coast to standstill
4=OFF3 - quick ramp-down
9=Fault acknowledge
10 =JOG right
Index:
P0701[0]: VSD in Auto mode
Dependency:
Setting 99 (enable BICO parameterization) requires P0700 (command source) or P3900 (end of quick commission-
ing)=1, 2 or P0970 (factory reset)=1 in order to reset
Note:
Setting 99 (BICO) for expert use only
P0702[2]
Function of digital input 2
Selects function of digital input 2
Unit: -
Min: 0
Detail:
See P0701 (function of digital input1)
P0703[2]
Function of digital input 3
Selects function of digital input 3
Unit: -
Min: 0
Detail:
See P0701 (function of digital input1)
P0704[2]
Function of digital input 4
Selects function of digital input 4
Unit: -
Min: 0
Detail:
See P0701 (function of digital input1)
P0705[2]
Function of digital input 5
Selects function of digital input 5 (via analog input)
Unit:
Min: 0
Detail:
See P0701 (function of digital input1)
P0706[2]
Function of digital input 6
Selects function of digital input 6 (via analog input)
Unit: _
Min: 0
Detail:
See P0701 (function of digital input1)
P0707[2]
Function of digital input 7
Selects function of digital input 7 (via analog input)
Unit: -
Min: 0
Settings:
0=Digital input disabled
1=ON/OFF1
2=ON reverse /OFF1
3=OFF2 - coast to standstill
4=OFF3 - quick ramp-down
9=Fault acknowledge
Index:
P0707[0]: VSD in Auto mode
Dependency:
Signals about 4 V are active, signals below 1.6 V are inactive
Note:
Signals above 4 V are active, signals below 1.6 V are inactive
P0708[2]
Function of digital input 8
Selects function of digital input 8 (via analog input)
Unit: -
Min: 0
Detail:
See P0707 (function of digital input7)
P0718
CO/BO: Hand / Auto
Mode after startup
Unit: -
Min: 0
r0722
CO/BO: Binary input values
Displays status of digital inputs
Unit: -
Min: -
Bit fields:
Bit00
Bit01
Bit02
Bit03
Bit04
Bit05
Siemens Building Technologies
HVAC Products
Def: 2
Def: 1
11=JOG left
12=Reverse
13=MOP up (increase freq.)
14=MOP down (decrease freq.)
15=Fixed setpoint (direct selection)
16=Fixed setpoint (direct selection + ON)
17=Fixed setpoint (binary coded selection+ON)
Def: 12
Def: 9
Def: 15
Def: 15
Def: 29
Def: 0
Def: 0
Def: 0
Def: -
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Digital input 5
Digital input 6
Commissioning Guide
10 Parameterization
Max: 6
2=Terminal
4=USS on BOP link
P0700[1]: VSD in Hand mode
Max: 99
P0701[1]: VSD in Hand mode
Max: 99
Max: 99
Max: 99
Max: 99
Max: 99
Max: 99
10 =JOG right
11 =JOG left
12 =Reverse
13 =MOP up (increase freq.)
14 =MOP down (decrease freq.)
P0707[1]: VSD in Hand mode
Max: 99
Max: 1
Max: -
0
OFF, 1
0
OFF, 1
0
OFF, 1
0
OFF, 1
0
OFF, 1
0
OFF, 1
5=USS on COM link
6=CB on COM link
25=DC brake enable
26=Enable essential service
27=Enable PID
28=Bypass mode command input
29=External trip
33=Disable additional freq setpoint
99=Enable BICO parameterization
25 =DC brake enable
26 =Enable essential service
29 =External trip
33 =Disable additional freq. setpoint
99 =Enable BICO parameterization
ON
ON
ON
ON
ON
ON
Level 1
Level 2
Level 2
Level 2
Level 2
Level 2
Level 2
Level 3
Level 3
Level 3
Level 3
55/80
CM1G5192en
26.02.2003