Application Example 2; Parameter Changes - Siemens sed2 Commissioning Manual

Variable speed drives
Hide thumbs Also See for sed2:
Table of Contents

Advertisement

7.2 Application example 2

A motor shall run at 4 fixed speeds.
Control is accomplished via digital inputs
Error message via relay output 1
Indication of operation via relay output 2
Note:
With the settings for this application example, the assumption is made that the parameters use their de-
fault values and that the connected motor has been commissioned with the standard parameters.
If several digital inputs are active at the same time, the setpoint will be added up.
The VSD is started when one of the inputs assumes the ON position.
L1
L2
L3
PE

7.2.1 Parameter changes

Start with quick commissioning according to application example 1
Par. no.
Value
P0003
3
P0701(0)
16
P0702(0)
16
P0703(0)
16
P0704(0)
16
P1000
3
P1001
10 Hz
P1002
20 Hz
P1003
30 Hz
P1004
40 Hz
Siemens Building Technologies
HVAC Products
Fuses
L1 L2 L3
Error
20
21
Com
22
23
SED2
Run
24
P(1)
Com
25
Hz
9
I
Hand
Fn
5
0
Auto
P
6
7
8
u
v
w
Inspection switch
Fan
M
Parameter function
User access level
VSD starts with fixed frequency 1
VSD starts with fixed frequency 2
VSD starts with fixed frequency 3
VSD starts with fixed frequency 4
Selection of frequency setpoint
Selection fixed frequency setpoint (Hz)
Selection fixed frequency setpoint (Hz)
Selection fixed frequency setpoint (Hz)
Selection fixed frequency setpoint (Hz)
Commissioning Guide
7 Application examples
Relay 1
Relay 2
Fixed frequency 1
Fixed frequency 2
Fixed frequency 3
Fixed frequency 4
Building Management System (BMS)
or
speed selector switch
DIP switch setting
ON
❚ ❚
OFF
1
2
Function selection
Expert access
(2 = analog, 3 = digital)
5192A02en
1 = analog input 1
OFF = DC 0...10 V
ON = 0...20 mA
2 = analog input 2
OFF = DC 0...10 V
ON = 0...20 mA
CM1G5192en
26.02.2003
31/80

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents