Siemens sed2 Commissioning Manual page 44

Variable speed drives
Hide thumbs Also See for sed2:
Table of Contents

Advertisement

Error
Cause
F0022
The fault is caused by the following events:
Power stack fault
♦ (1) dc link overcurrent =short-circuit of
IGBT
♦ (2) short-circuit of dc link chopper
♦ (3) earth fault.
Ø Frame sizes A to C (1),(2),(3)
Ø Frame sizes D to E (1),(2)
Ø Frame size F (2)
Since all these faults are assigned to one
signal on the power stack, it is not possible to
establish which one actually occurred.
F0023
One phase is interrupted at the VSD output.
Fault at VSD
output
F0024
Ø Ventilation is inadequate
Rectifier
Ø Fan is inoperative
overtemperature
Ø Ambient temperature is too high
F0030
Ø Fan no longer works
Fan fault
F0041
Ø Motor data identification failed
Motor data identi-
Ø Alarm value = 0: Load is missing
fication failure
Ø Alarm value = 1: Current limit value
reached during identification
Ø Alarm value = 2: Identified stator resistance
less than 0.1 % or more than 100 %
Ø Alarm value = 3: Identified rotor resistance
less than 0.1 % or more than 100 %
Ø Alarm value = 4: Identified stator reactance
less than 50 % or more than 500 %
Ø Alarm value = 5: Identified main reactance
less than 50 % or more than 500 %
Ø Alarm value = 6: Identified rotor time con-
stant less than 10 ms or more than 5 s
Ø Alarm value = 7: Identified total leakage
reactance less than 5 % or more than 50 %
Ø Alarm value = 8: Identified stator leakage
reactance less than 25 % or more than
250%
Ø Alarm value = 9: Identified rotor leakage
reactance less than 25 % or more than
250%
Ø Alarm value = 20: Identified IGBT ON
voltage less than 0.5 or more than 10 V
Ø Alarm value = 30: Current controller at
voltage limit
Ø Alarm value = 40: Inconsistency of identi-
fied data set, at least one identification
failed
Percentage values based on impedance
Zb = Vmot,nom / sqrt(3) / Imot,nom.
F0051
Ø
Read or write failure while saving non-
Parameter
volatile parameter
EEPROM fault
F0052
Ø Read failure for power stack information or
Power stack fault
invalid data
F0053
Ø
Read failure for I/O EEPROM information
I/O EEPROM fault
or invalid data
F0054
Ø I/O print is not connected
Wrong I/O print
Ø Wrong I/O print is connected
Ø NO ID found on I/O print, no data
44/80
Siemens Building Technologies
HVAC Products
Commissioning Guide
9 Error messages
Diagnosis and troubleshooting
Check wiring of the 3 phases at the VSD output and at
the motor terminals
Check if the stator winding of the motor is interrupted
Replace the VSD
Check the following:
1. The fan must turn when the VSD is running
2. The pulse frequency (P1800) must be set to default
value 4 kHz
The fault cannot be masked while the options module
(AOP or BOP) is connected
Replace the fan
0:
Check if the motor is connect to the VSD
1-40: Check if the motor data in P304-311 are correct
Check the type of motor wiring required (star, delta)
Reset VSD to factory setting and reparameterize
1. Ensure firmware version (r0018) is version 1.17 or
higher and
2. Replace I/O board (contact customer service)
Check the data
Exchange the I/O module
Check data flow
Exchange I/O module
Res-
ponse
Off2
Off2
Off2
Off2
Off2
Off2
Off2
Off2
CM1G5192en