Additional parameters
Parameter
P0003
Access level
P1200
Flying restart
P0295 (access level 4)
VSD fan off delay
time
P1210
Automatic restart
P0010
P0970
Reset to
factory defaults
7
Application examples
7.1 Application example 1
The speed of a motor shall be controlled via the motor's potentiometer (hand) or using a analog signal via
an external control signal DC 0...10 V within the frequency range of 0...50 Hz.
ON and OFF via the digital input
−
Error message via relay output 1
−
Indication of operation via relay output 2
−
Note:
With the settings for this application example, the assumption is made that the parameters use their de-
fault values and that the connected motor has been commissioned with the standard parameters.
L1
L2
L3
PE
L1 L2 L3
P(1)
Hz
I
0
u
Siemens Building Technologies
HVAC Products
Default Set to
Function
1
3
Allows the user to have a higher access level
The following parameters require level 3 access, unless stated otherwise
0
1
Allows motor to start into a spinning load
E.g. fan being turned by the air flow
0
Defines VSD internal fan switch off delay time (after VSD has stopped)
30-
Set P0003 to 4, set P3950 to 46, then set P0295 to the time required in
3600 s
seconds
1
2
Allows VSD to start after a power cut
Auto restart requires constant on command (e.g. via a digital input)
0
30
This allows the VSD to be reset to factory defaults
0
1
The following parameters retain their values after a factory reset:
P0918 (CB address), P2010 (USS Baud rate),
P2011 (USS address)
Fuses
SED fault
20
24
Motor running
9
5
SED2
3
Hand
Fn
2
Auto
P
SED2
v
w
Inspection switch
M
Fan
3
Commissioning Guide
7 Application examples
A
B
DC 0...10 V
Building Management System
(BMS)
5192A01en
DIP switch setting
ON
1 = analog input 1
❚ ❚
OFF
OFF = DC 0...10 V
1
2
ON = 0...20 mA
2 = analog input 2
OFF = DC 0...10 V
ON = 0...20 mA