P0305
Rated motor current
Nominal motor current [A] from rating plate
Unit: A Min: 0.01
Dependency:
Can be changed only when P0010=1 (quick commissioning)
Depends also on P0320 (motor magnetization current)
Note:
For asynchronous motors, the maximum value is defined as the maximum VSD current (r0209).
For synchronous motors, the maximum value is defined as twice the maximum VSD current (r0209).
The minimum value is defined as 1/32 times VSD rated current (r0207).
P0307
Rated motor power
Nominal motor power [kW/hp] from rating plate
Unit: -
Min: 0.01
Dependency:
If P0100=1 ([kW],frequency default 50 Hz), values will be in [hp]
Can be changed only when P0010=1 (quick commissioning)
P0308
Rated motor cosPhi
Nominal motor power factor (cosPhi) from rating plate
Unit: -
Min: 0.000
Dependency:
Can be changed only when P0010=1 (quick commissioning)
Visible only when P0100=0 or 2, (motor power entered in [kW])
Setting 0 causes internal calculation of value (see r0332)
P0309
Rated motor efficiency
Nominal motor efficiency in [%] from rating plate
Unit: %
Min: 0.0
Dependency:
Can be changed only when P0010=1 (quick commissioning)
Visible only when P0100=1, (i.e. motor power entered in [hp])
Setting 0 causes internal calculation of value (see r0332)
Note:
P0309=100 % corresponds to superconducting
P0310
Rated motor frequency
Nominal motor frequency [Hz] from rating plate
Unit: Hz
Min: 12.00
Dependency:
Can be changed only when P0010=1 (quick commissioning)
The pole pair number is recalculated automatically if parameter is changed
P0311
Rated motor speed
Nominal motor speed [rpm] from rating plate
Unit: 1/min
Min: 0
Dependency:
Can be changed only when P0010=1 (quick commissioning)
Setting 0 causes an internal calculation of value
Required for V/f control with speed controller
Slip compensation in V/f control requires the rated motor speed for correct operation
The pole pair number is recalculated automatically if the parameter is changed
r0313
Motor pole pairs
Displays the number of motor pole pairs that the VSD is currently using for internal calculations
Unit: -
Min: -
Value:
r0313=1 : 2-pole motor
Dependency:
Recalculated automatically when P0310 (rated motor frequency) or P0311 (rated motor speed) is changed
P0340
Calculation of motor parameters
Calculates various motor parameters, including:
Unit: -
Min: 0
Data:
Calculates various motor parameters, including:
• Motor weight
• Magnetization time
• Demagnetization time P0347 (level 3)
Settings:
0=No calculation
1=Complete parameterization
2=Calc. equivalent circuit data
Note:
This parameter is required during commissioning to optimize the VSD's performance
P0350
Stator resistance (line to line)
Stator resistance value in [Ohms] for the connected motor (from line to line). The parameter
value includes the cable resistance
Unit: Ohm
Min: 0.00001
Data:
Stator resistance value in [Ohms] for the connected motor (from line to line). The parameter value includes the cable
resistance. There are 3 ways to determine the value for this parameter:
1. Calculate using P0340=1 (data entered from rating plate) or P3900=1,2 or 3 (end of quick commissioning)
2. Measure using P1910=1 (motor data identification - value for stator resistance is overwritten)
3. Measure manually using an Ohmmeter
Note:
Since measured line to line, this value may appear to be higher (up to 2 times higher) than expected
The value entered in P0350 (stator resistance) is the one obtained by the method last used
r0395
CO: Total stator resistance [%]
Displays stator resistance of motor as [%] of combined stator / cable resistance
Unit: %
Min: -
Siemens Building Technologies
HVAC Products
Def: 3.25
Def: 0.75
Def: 0.000
Def: 0.0
Def: 50.00
Def: 0
Def: -
Def: 0
P0344 (level 3)
P0346 (level 3)
Def: 4.0
Def: -
Commissioning Guide
10 Parameterization
Max: 10000.00
Max: 2000.00
Max: 1.000
Max: 99.9
Max: 650.00
Max: 40000
Max: -
r0313=2: 4-pole motor, etc.
Max: 4
• Stator resistance
P0350 (level 2)
• Reference frequency P2000 (level 2)
• Reference current
P2002 (level 3)
3=Calc. V/f
4=Calc. only controller setting
Max: 2000.0
Max: -
Level 1
Level 1
Level 3
Level 3
Level 1
Level 1
Level 3
Level 3
Level 3
Level 3
53/80