7.3 Application example 3

Temperature control: Cooling
When the demand for cooling increases, the fan will increase its speed
Switching on / off via digital input 1 (thermostat), on temperature rise ON
External alarm to digital input 2 (e.g. fire alarm); fan stops in the event of an alarm
Error message via relay output 1
Indication of operation via relay output 2
L1
L2
L3
PE
L1
L2
P(1)
Hz
I
Hand
0
Auto
SED2
u
M
3

7.3.1 Parameter changes

Start with quick commissioning according to application example 1
Par. no.
Value
Parameter function
P0003
3
User access level
P0702(0)
29
Function of digital input 2 in "Auto" mode
P0702(1)
29
Function digital input 2 in "Hand" mode
P701(0)
16
Function of digital input 1
P2201
22 °C
Room temperature setpoint
P2253(0)
2224
Setpoint source for PID setpoint
P501(1)
29
Selection of temperature sensor
P2264(0)
755.1
PID feedback
P2306
0
Selection of cooling / heating sequence
P2200(0)
1
Enable PID controller
P2280
10
PID proportional gain
P2285
30
PID integral action time
r2262
Current setpoint
r2272
Current feedback
32/80
Siemens Building Technologies
HVAC Products
Fuses
L3
Error
20
21
Com
22
23
Run
24
Com
25
SED2
5
6
9
Fn
P
11
2
v
w
Inspection switch
Fan
Commissioning Guide
7 Application examples
Relay 1
Relay 2
Building Management System
DIP switch setting
ON
OFF
Function selection
Expert function
External alarm
External alarm
ON, fixed setpoint (thermostat)
Adjust required setpoint
Fixed PID setpoint
LG-Ni 1000: -50...150 °C
Analog input 2
Cooling
PID controller enabled
- Switch on/off
- External alarm
(BMS)
5192A03en
1 = analog input 1
❚ ❚
OFF = DC 0...10 V
1
2
ON = 0...20 mA
2 = analog input 2
OFF = DC 0...10 V
ON = 0...20 mA
CM1G5192en
26.02.2003