Parameter Changes - Siemens sed2 Commissioning Manual

Variable speed drives
Hide thumbs Also See for sed2:
Table of Contents

Advertisement

7.1.1 Parameter changes

Quick commissioning
Par. no.
Value
P0010
1
P0304
V
P0305
A
P0307
kW
P0310
Hz
P0311
rpm
≥ 10.00
P1080
P1082
Hz
P1120
20 s
P1121
30 s
P3900
1
Press
and then
Press
to access the display
Scaling of DC 0...10 V signals: Example: DC 0...10 V = 10...50 Hz
Par. no.
Value
P0003
2
P0757(0)
0
P0758(0)
20 %
P0759(0)
10
P0760(0)
100 %
Additional parameters
Change of motor's direction of rotation
Par. no.
Value
P0003
3
P1820
0/1
30/80
Siemens Building Technologies
HVAC Products
Parameter function
Start of quick commissioning
Rated motor voltage
Rated motor current
Rated motor power
Rated motor frequency
Rated motor speed
Minimum frequency
Maximum frequency
Ramp-up time
Ramp-down time
End of quick commissioning
to round up r0000
Parameter function
User access level
Value x1
Value y1
Value x2
Value y2
Parameter function
User access level
Reverse output phase sequence Select 0 or 1
Commissioning Guide
7 Application examples
Function selection
Quick commissioning
According to the motor's rating plate
According to the motor's rating plate
According to the motor's rating plate
According to the motor's rating plate
According to the motor's rating plate
Calculation of motor and end of quick commissioning
Function selection
Expert access
Minimum frequency at 0 V
Maximum frequency at 10 V
Function selection
Expert access
CM1G5192en
26.02.2003

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents