Danfoss ECL Comfort 210 Installation Manual page 95

A266
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
MENU > Settings > Control par.
Auto tuning
Circuit
All
Automatically determines the control parameters for the DHW control. 'Xp'
'Tn' and 'M run' do not need to be set, when using auto tuning. 'Nz' must
be set.
* See Appendix "Parameter ID overview"
OFF:
Auto tuning is not activated.
ON:
Auto tuning is activated.
The auto tuning function automatically determines the control
parameters for DHW control. Thus you do not need to set the 'Xp',
'Tn' and 'M run', as they are automatically set when the auto tuning
function is set to ON.
Auto tuning is typically used in connection with the installation of
the controller, but it can be activated when needed, e.g. for an
extra check of the control parameters.
Before starting the auto tuning, the tapping flow should be
adjusted to the relevant value (see table).
If possible, any additional DHW consumption should be avoided
during the auto tuning process. Should the tapping load vary too
much, the auto tuning and controller will return to the default
settings.
Auto tuning is activated by setting the function to ON. When the
auto tuning is ended, the function is automatically converted to
OFF (default setting). This will be indicated in the display.
The auto tuning process takes up to 25 minutes.
MENU > Settings > Control par.
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
Motor pr. (motor protection)
Circuit
All
Prevents the controller from unstable temperature control (and resulting
actuator oscillations). This can occur at very low load. The motor protection
increases the lifetime of all involved components.
* See Appendix "Parameter ID overview"
OFF:
Motor protection is not activated.
Value:
Motor protection is activated after the set activation
delay in minutes.
Danfoss District Energy
ECL Comfort 210 / 310, application A266
1x173
Setting range
Factory setting
*
1x174
Setting range
Factory setting
*
Heat
No. of
apartments
transfer
(kW)
1-2
30-49
*
3-9
50-79
10-49
80-149
50-129
150-249
130-210
250-350
In order to meet the summer- / winter variations, the ECL clock must
be set to the correct date for an successful auto tuning.
The motor protection function ('Motor pr.') has to be deactivated
during auto tuning. During auto tuning the circulation pump for tap
water must be switched off. This is done automatically if the pump is
controlled by the ECL controller.
Auto tuning is only applicable in connection with valves that are
approved for auto tuning, i.e. the Danfoss types VB 2 and VM 2 with
split characteristic as well as logarithmic valves such as VF and VFS.
Recommended for duct systems with variable load.
*
VI.KT.X3.02
Constant DHW draw-off (l / min)
3
(or 1 tap 25% open)
6
(or 1 tap 50% open)
12
(or 1 tap 100% open)
(or 1 tap 100% + 1 tap 50%
18
open)
24
(or 2 taps 100% open)
DEN-SMT/DK
95