Installation Guide
2.5.2 Electrical connections 24 V a.c.
See also the Mounting Guide (delivered with the application key)
for application specific connections.
Maximum load ratings:
Relay terminals
Triac (= electronic
relay) terminals
22
DEN-SMT/DK
ECL Comfort 210 / 310, application A266
4 (2) A / 24 V a.c.
(4 A for ohmic load, 2 A for
inductive load)
1 A / 24 V a.c.
Do not connect 230 V a.c. powered components to a 24 V a.c. power
supplied controller directly. Use auxilliary relays (K) to separate 230
V a.c. from 24 V a.c.
VI.KT.X3.02
Danfoss District Energy