Installation Guide
MENU > Settings > Optimization
Parallel operation
Circuit
All
Choose whether the heating circuit is to operate in dependence of the DHW
circuit. This function might be useful if an installation has limited power
or flow.
* See Appendix "Parameter ID overview"
OFF:
Independent parallel operation, i.e. the DHW and
the heating circuits operate independently of each
other. It makes no difference whether the desired DHW
temperature can be reached or not.
Value:
Dependent parallel operation, i.e. the desired heating
temperature depends on the DHW demand. Choose
how much the DHW temperature can drop before the
desired heating temperature has to be decreased.
90
DEN-SMT/DK
ECL Comfort 210 / 310, application A266
1x043
Setting range
Factory setting
*
Temp.
*
100%
Parallel operation with
parallel
decreased heating temp.
operation
If the actual DHW temperature deviates more than the set value, the
gear motor M2 in the heating circuit will gradually close to such an
extent that the DHW temperature stabilizes at the lowest acceptable
value.
In case the Parallel operation is active (a too low DHW temperature
and therefore a reduced heating circuit temperature), a slave's
temperature demand will not change the desired flow temperature in
the heating circuit.
When dependent parallel operation is in function:
Desired flow temperature for the heating circuit will be minimum
limited, when "Priority for return temperature" (ID 1x085) is set
to OFF.
Desired flow temperature for the heating circuit will not be
minimum limited, when "Priority for return temperature"
(ID 1x085) is set to ON.
VI.KT.X3.02
Acceptable deviation
Desired DHW temp.
Actual DHW temp.
Time