Danfoss ECL Comfort 210 Installation Manual page 76

A266
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Return limit
Con.T, re. T lim. (Constant temperature mode, return
temperature limitation)
Circuit
All
The "Con. T, ret. T limit" is the return temperature limitation value when the
circuit is set to override mode type "Const. T" (= Constant temperature).
* See Appendix "Parameter ID overview"
Value: Set the return temperature limitation
MENU > Settings > Return limit
DHW, ret. T limit
Circuit
All
When an addressed slave is active in DHW-tank heating / charging, the
return temperature limitation in the master can be set.
Notes:
The master circuit must be set to react on the desired flow temperature
in the slave(s). See "Demand offset" (ID 11017).
The slave(s) must be set to send its / their desired flow temperature to the
master. See "Send desired T" (ID 1x500).
* See Appendix "Parameter ID overview"
OFF:
No influence from slaves. The return temperature
limitation is related to settings in "Return limit".
Value: Return temperature limitation value when slave is in
DHW tank heating / charging operation.
76
DEN-SMT/DK
ECL Comfort 210 / 310, application A266
1x028
Setting range
Factory setting
*
1x029
Setting range
Factory setting
*
*
Override mode
When ECL Comfort is in Scheduled mode, a contact (switch) signal can
be applied to an input in order to override to Comfort, Saving, Frost
Protection or Constant temperature. As long as the contact (switch)
signal is applied, the override is active.
*
# 1 # = Master, example A266, address 15
# 2 # = Slave, example A237, address 9
# 3 # = Slave, example A367, address 6
Some examples of applications with DHW-tank heating / charging are:
A217, A237, A247, A367, A377
VI.KT.X3.02
Danfoss District Energy

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecl comfort 310Application a376