Danfoss ECL Comfort 210 Installation Manual page 113

A266
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
MENU > Alarm > Charge T
MENU > Alarm > Temp. monitor
Upper difference
Circuit
All
The alarm is activated if the actual flow / duct temperature increases more
than the set difference (acceptable temperature difference above the desired
flow / duct temperature). See also 'Delay'.
* See Appendix "Parameter ID overview"
OFF:
The related alarm function is not active.
Value:
The alarm function is active if the actual temperature
gets above the acceptable difference.
MENU > Alarm > Charge T
MENU > Alarm > Temp. monitor
Lower difference
Circuit
All
The alarm is activated if the actual flow / duct temperature decreases more
than the set difference (acceptable temperature difference below the desired
flow / duct temperature). See also 'Delay'.
* See Appendix "Parameter ID overview"
OFF:
The related alarm function is not active.
Value:
The alarm function is active if the actual temperature
gets below the acceptable difference.
MENU > Alarm > Charge T
MENU > Alarm > Temp. monitor
Delay
Circuit
All
If an alarm condition from either 'Upper difference' or 'Lower difference' is
present for a longer time than the set delay (in minutes), the alarm function
is activated.
* See Appendix "Parameter ID overview"
Value:
The alarm function will be activated if the alarm
condition remains after the set delay.
Danfoss District Energy
ECL Comfort 210 / 310, application A266
1x147
Setting range
Factory setting
*
1x148
Setting range
Factory setting
*
1x149
Setting range
Factory setting
*
Flow / duct temp. °C
*
Flow / duct temp. °C
*
Temp.
*
VI.KT.X3.02
Upper difference (set
value)
Desired flow / duct
temp.
Time
Lower difference (set
value)
Desired flow / duct
temp.
Time
Flow temp.
Alarm limit
Time
Delay
DEN-SMT/DK
113