Danfoss ECL Comfort 210 Installation Manual page 82

A266
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
MENU > Settings > Flow / power limit
Adapt. time (adaptation time)
Circuit
All
Controls how fast the flow / power limitation adapts to the desired
limitation.
* See Appendix "Parameter ID overview"
OFF:
The control function is not influenced by the 'Adapt.
time' .
1:
The desired temperature is adapted quickly.
50:
The desired temperature is adapted slowly.
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Flow / power limit
MENU > Settings > Refill tank
MENU > Settings > S7 (S8, S9, S10) pressure
Filter constant
Circuit
All
The value of the filter constant determines the dampening of the measured
value.
The higher the value, the more dampening.
By this, a too quick change of the measured value can be avoided.
* See Appendix "Parameter ID overview"
Minor
Lower dampening
value:
Major
Higher dampening
value:
MENU > Settings > Flow meter
MENU > Settings > Flow / power limit
Pulse
Circuit
All
Set the value of the pulses from the flow / heat meter.
* See Appendix "Parameter ID overview"
OFF:
No input.
1 ... 9999: Pulse value.
82
DEN-SMT/DK
ECL Comfort 210 / 310, application A266
1x112
Setting range
Factory setting
*
1x113
Factory setting
Setting range
*
1x114
Setting range
Factory setting
*
If the 'Adapt. time' is too low, there is a risk of unstable control.
*
*
Example :
One pulse can represent a number of litres (from a flow meter)
or a number of kWh (from a heat meter).
*
VI.KT.X3.02