Danfoss ECL Comfort 210 Installation Manual page 81

A266
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Flow meter
MENU > Settings > Flow / power limit
Input type
Circuit
All
Choice of input type from flow / heat meter
* See Appendix "Parameter ID overview"
OFF:
No input
IM1 -
Flow / heat meter signal based on pulses.
IM5:
EM1 -
Flow / heat meter signal from M-bus.
EM5:
MENU > Settings > Flow / power limit
Actual (actual flow or power)
Circuit
All
The value is the actual flow or power based on the signal from flow / energy
meter.
MENU > Settings > Control par., fan
MENU > Settings > Flow / power limit
Limit (limitation value)
Circuit
All
This value is in some applications a calculated limitation value, based on the
actual outdoor temperature.
In other applications the value is a selectable limitation value.
* See Appendix "Parameter ID overview"
Danfoss District Energy
ECL Comfort 210 / 310, application A266
1x109
Setting range
Factory setting
*
Setting range
Factory setting
1x111
Setting range
Factory setting
*
Pulse based signal for flow / energy, applied to input S7
For monitoring:
Frequency range is 0.01 - 200 Hz
For limitation:
Minimum frequency is recommended to be 1 Hz in order to have a
stable control. Furthermore, the pulses must appear regularly.
The setting range for IM and EM depends on chosen subtype.
*
*
VI.KT.X3.02
DEN-SMT/DK
81