Installation Guide
MENU > Alarm > Charge T
MENU > Alarm > Temp. monitor
Lowest temp.
Circuit
All
The alarm function will not be activated if the desired flow / duct
temperature is lower than the set value.
* See Appendix "Parameter ID overview"
MENU > Alarm > Pressure
Low X — A266.9
Circuit
1
The pressure is measured by means of a pressure transmitter. The transmitter
sends the measured pressure as a 0-10 V or a 4-20 mA signal.
A voltage signal can be applied directly to input S7. A current signal is
converted by means of a resistor to a voltage and then applied to input S7.
The measured voltage on input S7 must be converted to a pressure value by
the controller. This and following 3 settings set up the scaling.
'Low X' defines the voltage value for the lowest pressure value ('Low Y').
MENU > Alarm > Pressure
High X — A266.9
Circuit
1
The measured voltage on input S7 must be converted to a pressure value.
High X defines the voltage value for the highest pressure value ('High Y').
MENU > Alarm > Pressure
Low Y — A266.9
Circuit
1
The measured voltage on input S7 must be converted to a pressure value.
Low Y defines the pressure value for the lowest voltage value ('Low X').
MENU > Alarm > Pressure
High Y — A266.9
Circuit
1
The measured voltage on input S7 must be converted to a pressure value.
High Y defines the pressure value for the highest voltage value ('High X').
114
DEN-SMT/DK
ECL Comfort 210 / 310, application A266
1x150
Setting range
Factory setting
*
11607
Setting range
Factory setting
0.0 ... 10.0
1.0
11608
Setting range
Factory setting
0.0 ... 10.0
5.0
11609
Setting range
Factory setting
0.0 ... 10.0
0.0
11610
Setting range
Factory setting
0.0 ... 10.0
6.0
If the cause of the alarm disappears, the alarm indication and output
also disappear.
*
Example: Relationship between input voltage and indicated pressure
Pressure (bar)
6.0
High Y
0.0
Low Y
1
Low X
This example shows that 1 volt corresponds to 0.0 bar and 5 volt correspond
to 6.0 bar.
VI.KT.X3.02
Volt
5
High X