Installation Guide
MENU > Settings > Flow meter
MENU > Settings > Flow / power limit
Units
Circuit
All
Choice of units for measured values.
* See Appendix "Parameter ID overview"
Units to the left: pulse value.
Units to the right: actual and limitation values.
The value from the flow meter is expressed as ml or l.
The value from the heat meter is expressed as Wh, kWh, MWh or
GWh.
The values for the actual flow and the flow limitation are expressed
as l/h or m³/h.
The values for the actual power and the power limitation are
expressed as kW, MW or GW.
MENU > Settings > Flow / power limit
High limit Y2 (flow / power limitation, high limit, Y-axis)
Circuit
All
Set the flow / power limitation referring to the outdoor temperature set
in 'Low T out X2'.
* See Appendix "Parameter ID overview"
The corresponding X coordinate is set in 'Low T out X2'.
Danfoss District Energy
ECL Comfort 210 / 310, application A266
1x115
Factory setting
Setting range
*
1x116
Setting range
Factory setting
*
Pulse based signal for flow / energy, applied to input S7
For monitoring:
Frequency range is 0.01 - 200 Hz
For limitation:
Minimum frequency is recommended to be 1 Hz in order to have a
stable control. Furthermore, the pulses must appear regularly.
List for setting range of 'Units':
ml, l/h
l, l/h
*
ml, m³/h
l, m³/h
Wh, kW
kWh, kW
kWh, MW
MWh, MW
MWh, GW
GWh, GW
Example 1:
'Units' (11115):
l, m³/h
'Pulse' (11114):
10
Each pulse represents 10 litres and the flow is expressed as cubic
meters (m³) per hour.
Example 2:
'Units' (11115):
kWh, kW (= kilo Watt hour, kilo Watt)
'Pulse' (11114):
1
Each pulse represents 1 kilo Watt hour and the power is
expressed in kilo Watt.
*
VI.KT.X3.02
DEN-SMT/DK
83