A266.10, in general:
Alarm A1 (= relay 4) can be activated:
if the temperature at S3 exceeds an alarm value
if the alarm input S8 is activated
If the temperature at S3 exceeds the alarm value 'Max. flow T', the
circulation pump P2 is switched OFF after elapse of the 'Delay'.
P2 is switched ON again when the temperature at S3 gets below
alarm value.
When the subtype A266.10 has been uploaded, the ECL Comfort
controller starts in scheduled mode.
A266, in general:
Up to two Remote Control Units, ECA 30 / 31 can be connected to
one ECL controller in order to control the ECL controller remotely.
Exercise of circulation pumps and control valve in periods without
heating demand can be arranged.
Additional ECL Comfort controllers can be connected via the ECL
485 bus in order to utilize common outdoor temperature signal,
time and date signals. The ECL controllers in the ECL 485 system
can work in master - slave system.
Unused input can, by means of an override switch, be used to
override the schedule to a fixed 'Comfort' or 'Saving' mode.
Modbus communication to a SCADA system can be established.
The M-bus data (ECL Comfort 310) can furthermore be transferred
to the Modbus communication.
Alarm A1 (= relay 4) can be activated:
if a temperature sensor or its connection disconnects / short
circuits. (See: Common controller settings > System > Raw
input overview).
Danfoss District Energy
ECL Comfort 210 / 310, application A266
The controller is pre-programmed with factory settings that are shown
in the 'Parameter ID overview' appendix.
VI.KT.X3.02
DEN-SMT/DK
13