Installation Guide
To find the reason for an alarm:
select MENU
select 'Alarm'
select 'Alarm overview' . A "bell" will be shown at the alarm in
question.
Alarm overview (example):
2: Max. temp.
3: Temp. monitor
32: T sensor defect
The numbers in the 'Alarm overview' refer to the alarm number
in the Modbus communication.
To reset an alarm:
When the "bell" is present to the right of the alarm line, place the
cursor at the alarm line in question and press the dial.
To reset alarm 32:
MENU > Common controller settings > System > Raw input
overview: The sensor in question is marked and the alarm can be
reset.
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Alarm > Max. temp.
Max. flow T (Maximum flow temperature)
Circuit
All
The maximum acceptable flow temperature is set here.
When the flow temperature gets higher than the set value, the alarm symbol
/ relay go ON.
When the flow temperature gets 5 K below the set value, the alarm symbol /
relay go OFF.
* See Appendix "Parameter ID overview"
Value: Set the acceptable maximum flow temperature
MENU > Alarm > Max. temp.
Delay
Circuit
All
If an alarm condition from 'Max. flow T' is present for a longer time than the
set delay (in seconds), the alarm function is activated.
* See Appendix "Parameter ID overview"
Value: The alarm function will be activated if the alarm condition
remains after the set delay.
112
DEN-SMT/DK
ECL Comfort 210 / 310, application A266
1x079
Setting range
Factory setting
*
1x080
Setting range
Factory setting
*
Also observe the settings:
* Delay' (ID 1x080)
*
Also observe the settings:
* 'Max. flow T' (ID 1x079)
*
VI.KT.X3.02