Installation Guide
MENU > Settings > Flow temperature
MENU > Settings > Tank temperature
Desired T
Circuit
All
When the ECL Comfort is in override mode, type "Const. T", the desired flow
temperature can be set.
A "Const. T" related return temperature limitation can also be set. See MENU
> Settings > Return limit > 'Con. T, ret. T lim. '
* See Appendix "Parameter ID overview"
MENU > Settings > Flow temperature
MENU > Settings > Inlet temperature
Temp. min. (duct / flow / inlet temp. limit, min.)
Circuit
All
* See Appendix "Parameter ID overview"
Set the min. duct / flow / inlet temperature for the system. The
desired duct / flow / inlet temperature will not be lower than this
setting. Adjust the factory setting, if required.
MENU > Settings > Flow temperature
MENU > Settings > Inlet temperature
Temp. max. (duct / flow / inlet temp. limit, max.)
Circuit
All
* See Appendix "Parameter ID overview"
Set the max. flow / duct / inlet temperature for the system. The
desired temperature will not be higher than this setting. Adjust
the factory setting, if required.
70
DEN-SMT/DK
ECL Comfort 210 / 310, application A266
1x004
Setting range
Factory setting
*
1x177
Setting range
Factory setting
*
1x178
Setting range
Factory setting
*
Override mode
When ECL Comfort is in Scheduled mode, a contact (switch) signal can
be applied to an input in order to override to Comfort, Saving, Frost
Protection or Constant temperature. As long as the contact (switch)
*
signal is applied, the override is active.
The "Desired T" value can be influenced by:
temp. max.
temp. min.
room temp. limit
return temp. limit
flow / power limit
'Temp. min. ' is overruled if 'Total stop' is active in Saving mode or
'Cut-out' is active.
'Temp. min. ' can be overruled by the influence from the return
temperature limitation (see 'Priority').
*
The setting for 'Temp. max. ' has higher priority than 'Temp. min. ' .
The setting of 'heat curve' is possible for heating circuits only.
*
The setting for 'Temp. max. ' has higher priority than 'Temp. min. ' .
VI.KT.X3.02
Danfoss District Energy