5.3.3 MMF-300 Wiring for Emergency Alarm System Applications
Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the
required SLC address. Refer to "Setting an SLC address for a Single Point Module" on page 34.
The figure below shows typical wiring for a supervised and power-limited Emergency Signaling
circuit using an MMF-300 module.
See "Power Considerations" on page 68 for information on supervising 24 VDC power.
See Section 6, "Control Modules" for instructions on using control modules as NACs on an
SLC.
For compatible output devices refer to the Device Compatibility Document #15384.
47K ELR
(supplied
with module)
UL-listed Signaling
applicance such as the
Fire-Lite FSS-2400E
38
IDC
Figure 5.11 Emergency Signaling Wiring with an MMF-300
SLC
MMF-300 Module
programmed for Tornado,
Hazard, or Medical operation.
Refer to the control panel
installation manual.
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
MMF-300 Wiring Diagrams
-
+
-
+