6: Features Not Supported; 7: Circuit Board Information - Honeywell SLC Installation Manual

Intelligent control panel
Table of Contents

Advertisement

Control Modules
6.4.6 Features Not Supported
The "Synchronization" and "Power Supply Monitoring" features are not supported at this time.
6.4.7 Circuit Board Information
Status Indicators
Green LEDs are
controlled by FACP to
indicate status of each
module address.
Place shunt onto required pins.
Remove shunt for Style Z (Class A).
50
Synchronization Generator -
Not Supported. DO NOT
remove shunts.
Disable Address -
Select
Style Y (Class B) or
Style Z (Class A) -
Figure 6.4 CMF-300-6 Control Module Settings
#1 #2
#3
#4
#5
SLC Address
Set rotary switches to
address required.
Short Circuit Protection - Remove
shunt from the corresponding pins to
enable. Shunt #1 for first address, #2
for second address, etc.
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
CMF-300-6 Installation
Power Supply Monitors -
Not Supported. DO NOT
remove shunts.
#6