2: Wiring A Style Z Nac (Four-Wire) - Honeywell SLC Installation Manual

Intelligent control panel
Table of Contents

Advertisement

Control Modules
6.5.2 Wiring a Style Z NAC (Four-Wire)
A supervised and power-limited NFPA Style Z (Class A) NAC with a single power supply dedi-
cated to a single NAC using a CMF-300-6 module. Polarized alarm notification appliances are
shown connected to the module in a four-wire configuration.
NOTE: Refer to the Device Compatibility Document for compatible notification appliances and
relays.
See "Power Considerations" on page 68 for information on monitoring 24 VDC power.
Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive
load (on mechanical bells and horns).
24 VDC power must be provided from a UL listed power supply for fire protection use.
A power supervision relay is required only on the last module of the power run.
Do not T-tap or branch a Style Z circuit.
Do not loop wiring under the screw terminals of any notification appliance. To maintain
supervision, break the wire run at each device.
Power Supervision
Relay
(EOLR-1)
SLC
Figure 6.6 NFPA Style Z Notification Appliance Circuit
52
24 VDC notification appliances
NAC
Return
CMF-300-6
Power Supply Jumper
Relay Connector Assembly
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
Wiring a CMF-300-6 Module
24 VDC
nonresettable
power
NAC
Out

Hide quick links: