MMF-302-6 Wiring Diagrams
5.7.2 Wiring a NFPA Style D IDC with an MMF-302-6
Connect the SLC wiring to the module terminals T0 as shown below.
Use the rotary switches on the module to set it to the SLC addresses. Each module takes three alter-
nating addresses on the SLC. The remaining module points are automatically assigned to the next
two higher addresses. (Example: 28, 30 and 32). Refer to "Setting an SLC address for a Multi-
Point Module" on page 35.
DO NOT set the lowest address above 150 (41 for the MS-9050UD, 90 for the MS-9200, MS-
9200UD, and MS-9200UDLS), as the other module points will be assigned to nonexistent
addresses.
The figure below shows typical wiring for a supervised and power-limited NFPA Style D (Class A)
IDC using an MMF-302-6 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
24 VDC power must be provided from a UL listed power supply for fire protection use. This
power is inherently supervised by the module.
See "Power Considerations" on page 68 for information on 24 VDC power.
SLC
Figure 5.18 Typical Style D IDC Wiring with an MMF-302-6
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
Two-wire smoke detectors
24 VDC resettable power
IDC
Return
MMF-302-6
Monitor Modules
IDC
Out
45