MMF-302 Wiring Diagrams
5.6.2 Wiring a NFPA Style D IDC with an MMF-302
Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the
required SLC address. Refer to "Setting an SLC address for a Single Point Module" on page 34.
The figure below shows typical wiring for a supervised and power-limited NFPA Style D (Class A)
IDC using an MMF-302 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
24 VDC power must be provided from a UL listed power supply for fire protection use. This
power is inherently supervised by the module.
See "Power Considerations" on page 68 for information on 24 VDC power.
Two-wire
smoke
detectors
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
24 VDC Resettable power.
90 mA External 24 volt supply required
IDC
3.9K ELR
(supplied with module)
Figure 5.16 Typical Style D IDC Wiring with an MMF-302
SLC
MMF-302
Monitor Modules