Wiring the W-GATE
9.7.2 W-GATE Powered by the SLC
The W-GATE provides isolation of short circuits on the SLC in Class A (Style 6) installations. SLC
connections are power-limited by the panel. An interruption in the SLC that causes a loss of power
at the W-GATE for more than 100ms may result in a trouble condition and loss of fire protection
provided by the wireless devices for approximately 15 minutes. Use of a regulated, external
+24VDC power source (not SLC power) is recommended for installations that require fire protec-
tion in the presence of short circuits, including Class A applications and applications that use isola-
tor modules. Figure 9.6 shows typical wiring of a Wireless Network Gateway connected to an SLC
when power is supplied by the SLC loop
SLC out to next device (Class B)
or SLC return to FACP (Class A)
SLC in from FACP/device
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
A7- SLC OUT+
A6- SLC IN+
A5- SLC- (Common)
A4- SLC Power Select 2
A3- Power +24VDC
A2- Power Ground
A1- SLC Power Select 1
Figure 9.5 W-GATE Mounting Plate - Terminal Layout
+
-
+
-
Jumpers
Figure 9.6 W-GATE Powered by the SLC
Intelligent Detector Bases and Wireless Gateway
63