Introduction
For information on...
D350RP Duct Detector w/Relay
D350RPL(A) Duct Detector w/Relay - low flow
D355PL Duct Detector - low flow
BEAM355(S) Addressable Beam Detector
B210LP Plug-in Detector Base
B501 Detector Base
B501BH Sounder Detector Base
B501BH-2 Sounder Detector Base
B501BHT Temporal Sounder Detector Base
B501BHT-2 Temporal Sounder Detector Base
B200SR Sounder Detector Base
B200SR-LF Low Frequency Sounder Detector Base
B224RB Relay Detector Base
B224BI Isolator Detector Base
1.2 Overview
Communication between the control panel and intelligent addressable monitor and control devices
takes place through a Signaling Line Circuit (SLC), which can be wired to meet the requirements of
NFPA Style 4, Style 6, or Style 7.
At least one secondary surge protector must be used with each SLC wiring pair whenever SLC
wiring runs outside the building. For detailed information refer to "Surge Suppression" on page 71.
1.3 Polling Protocols
The MS-9200UDLS, MS-9600LS, and MS-9600UDLS support LiteSpeed protocol or Classic
Loop Interface Protocol (CLIP). The MS-9200/E, MS-9600/E, MS-9200UD/E, and MS-9050UD
support Classic Loop Interface Protocol (CLIP) only.
1.3.1 Available Protocols
LiteSpeed is a communication protocol that greatly enhances the speed of communication between
analog intelligent devices. Only the MS-9200UDLS, MS-9600LS, and MS-9600UDLS are capable
of operating in LiteSpeed mode. This is the default mode of operation for these FACPs.
CLIP (Classic Loop Interface Protocol) polls devices in sequential order. All Fire-LiteFireWarden
addressable fire alarm control panels can operate in CLIP mode. This is the default mode of
operation for all other FACPs.
1.3.2 Protocol Use
Use one of the following options with LiteSpeed/CLIP mode:
1.
Program all modules and detectors on an FACP as LiteSpeed.
2.
Program all modules and detectors on an FACP as CLIP.
NOTE: FACPs with more than one SLC loop must be programmed for only LiteSpeed or CLIP
mode of operation. Communication protocols cannot be split between SLC loops.
When switching between polling protocols, the loop circuit must be powered down for at least 30
seconds to reset the devices.
10
Table 1.1 Reference Documentation
Refer to...
Installation Instructions
Installation Instructions
Installation Instructions
Installation Instructions
Installation Instructions
Installation Instructions
Installation Instructions
Installation Instructions
Installation Instructions
Installation Instructions
Installation Instructions
Installation Instructions
Installation Instructions
Installation Instructions
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
Overview
Part Number
I56-0047
I56-1974
I56-3255
I56-2425
I56-3739
I56-0357 / I56-3738
I56-0491
I56-2813
I56-1367
I56-2819
I56-3387
I56-4152
I56-2815 / I56-3737
I56-0725 / I56-3736