A separate electrical circuit must be run from
the main electrical service with an over-
current device/disconnect in the circuit. A
service switch is recommended and may be
required by some local jurisdictions. Locate
the service switch such that the appliance can
be shut off without exposing personnel to
danger in the event of an emergency. See
Table 3 for available voltages.

Table 3: Electrical Requirements

ARC1000
Voltage
FLA
CCA
120/1/60
6.6
2.6
ARC1500
Voltage
FLA
CCA
208-
6.9
2.6
240/1/60
ARC2000 to ARC3000
Voltage
FLA
CCA
208-
8.3
2.6
240/1/60
208-
9.5
2.6
240/3/60
480/3/60
6.6
2.6
FLA = Full Load Amps : CCA = Control
Circuit Amps : MHP = Motor Horse Power :
MA = Motor Amps
Connect field supplied safety limits or devices
using proper terminals provided in boiler
electrical cabinet. Refer to wiring diagram
supplied with boiler for wiring information.
See Appendix G for sample-wiring diagrams.
An as-built wiring diagram is included with
every boiler when it ships. Contact a Thermal
Solutions Representative or visit the website
(www. thermalsolutions.com) for current
wiring options.
Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web:
Phone: 717-239-7642 Fax: 877-501-5212 Email:
21
MHP
MA
.46
4
MHP
MA
1.1
4.3
MHP
MA
1.5
5.7
3
6.9
3.2
4

3.5.2 Gas Supply Requirements

Refer to Table 4 for minimum and maximum
gas supply pressure. When the gas supply
pressure exceeds the maximum, an additional
field supplied regulator will be required to
reduce the supply pressure. For proper gas
supply sizing refer to Appendix A.
Capacity
Model
(SCFH)
ARC1000
1000
ARC1500
1500
ARC2000
2000
ARC2500
2500
ARC3000
3000

Table 4: Gas Supply Requirements

3.5.3 Sound Pressure Levels

Sound pressure levels were measured at 4-
1/2' above the floor and 3' from the boiler at
the front, rear and two sides. See Table 5 for
decibel readings.

Table 5 Sound Pressure Levels

Model
Front
ARC1000
ARC1500
67
ARC2000
67
ARC2500
62
ARC3000
62
www.thermalsolutions.com
sales@thermalsolutions.com
Form: 2435
Revision: 8
Date: 9-19-2016
Inlet
Min.
Max.
(nps)
(iwc)
(iwc)
1
4
14
2
4
14
2
4
14
2
4
14
2
4
14
Decibel Levels
Tube
Right
Rear
Side
Side
60
61
63
60
61
63
62
66
61
62
66
61