Arctic Installation and Operation Manual
installed in this line from the boiler to point
of discharge.
The condensate drain trap should be flushed
with water as part of your boiler maintenance
schedule to remove any debris that might
have accumulated over time.
A common condensate pump/sump may be
used. Run separate piping from each
condensate drain to the sump. A common
drain may be used to discharge condensate
from the sump. Consult pump/sump
materials of construction. If a common sump
is used, individual drain lines should be
connected such that one drain cannot back
feed into another drain. Use Table 2 for
sizing the pump / sump.

Table 2: Typical Condensate Flow Rate

Model
Max Condensate Flow (gph)
ARC1000
ARC1500
ARC2000
ARC2500
ARC3000
Consult local authorities regarding disposal of
flue gas condensate into public waste water
system. Some jurisdictions require that
condensate be buffered before discharge. This
buffering is commonly achieved by draining
the condensate through a limestone bed.
Consult Thermal Solutions or a chemical
treatment company for buffering system.
CAUTION
Failure to properly pipe the condensate
system will greatly reduce boiler life. Do
not install plugs, caps, or valves on
condensate piping.
Do not manifold boiler condensate and
vent drains together.
Do not crimp condensate lines or reduce
drain line inner diameter size.
Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web:
Phone: 717-239-7642 Fax: 877-501-5212 Email:
12
7
10.5
16
21.5
27

3.2.5.1 ARC1000 Condensate Drain Trap

Ensure that the condensate drain trap is filled
with water prior to running the boiler to
prevent flue gas emission to the boiler room.
It is recommended that the personnel
responsible for running and maintaining the
boiler periodically check the water level in the
condensate drain trap bend, especially, when
the boiler is operating in a non-condensing
condition for an extended period of time.
Figure 4: ARC 1000 Condensate Drain
Trap
1. Union Connection to the boiler
condensate drain line
2. Removable cleaning plug
3. Condensate drain outlet connection
3.2.5.2 ARC1500 – 3000 Condensate Drain
Trap
www.thermalsolutions.com
sales@thermalsolutions.com
Form: 2435
Revision: 8
Date: 9-19-2016