Combustion Air And Venting Requirements For Canada; Air Supply Requirements Per Can/Csa-B149.1-05 For Appliances Having An Input; Exceeding 400 Mbh - Thermal Solutions Arctic Installation & Operation Manual

Table of Contents

Advertisement

by manufacturer for installation of the
Arctic Installation and Operation Manual
equipment and the venting system
shall include:
i.
Detailed instructions for the
installation of the venting system
design or the venting system
components; and
ii. A complete parts list for the vent
system design or venting system.
c. MANUFACTURER REQUIREMENTS-
GAS EQUIPMENT VENTING SYSTEM
NOT PROVIDED. When the
manufacturer of a Product Approved
side wall horizontally vented gas
fueled equipment does not provide
the parts for venting the flue gases,
but identifies "special venting
systems", the following requirements
shall be satisfied by the manufacturer:
i.
The referenced "special venting
system" instructions shall be
included with the appliance or
equipment installation
instructions; and
ii. The "special venting systems"
shall be Product Approved by the
Board, and the instructions for the
system shall include a parts list
and detailed installation
instructions.
d. A copy of all installation instructions
for all Product Approved side wall
horizontally vented gas fueled
equipment, all venting instructions, all
parts lists for venting instructions,
and/or all venting design instructions
shall remain with appliance or
equipment at the completion of the
installation instructions.
Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web:
Phone: 717-239-7642 Fax: 877-501-5212 Email:
19
3.4.2 Combustion Air and Venting
Requirements for Canada
Canadian Standard CAN/CSA-B149.1-05,
Natural gas and propane installation code
specifies venting systems and air supply for
appliances in Section 8. Paragraph 8.1.4 states
"Air supply shall be provided in accordance
with Clause 8.4 when either an appliance or a
combination of appliances has a total input
exceeding 400,000 Btuh. Air supply is defined
as combustion air, excess air, flue gas dilution
air, primary air, secondary air, and ventilation
air. The air supply requirements below are a
summation of Clause 8.4 specific to this
boiler.
3.4.2.1 Air Supply Requirements per
CAN/CSA-B149.1-05 for
Appliances having an input

exceeding 400 MBH.

Ventilation Air: an opening for ventilation air
at the highest point that opens to the
outdoors shall provide Ventilation of the
space. The cross sectional area of this
opening shall be at least 10% of the area
required for combustion air, but in no case
shall the cross-sectional area be less that 10 in
2
(6500mm
).
Combustion Air: For combustion air where
the air supply is provided by natural airflow
from outdoors, in addition to the opening for
ventilation air, there shall be permanent
opening having a total cross-sectional free
area of not less than 1 in
BTU/hr. (70 mm
2
for each kW) of the total
rated input of the boiler(s). The location of
the opening(s) shall not interfere with the
openings for ventilation air. Please refer to
CAN/CSA-B149.1-05, Para. 8.4.4, for
combustion air openings if there are natural
draft, fan assisted or power draft assisted
equipment in the space.
When an air supply duct is used to supply
combustion air, it's discharge opening shall be
www.thermalsolutions.com
sales@thermalsolutions.com
Form: 2435
Revision: 8
Date: 9-19-2016
2
2
for each 30,000