Arctic Installation and Operation Manual

3.5.4 Pump and Piping Requirements

Pump piping and system piping must meet
the requirements of local codes and
jurisdictions. Good engineering practices
should be followed and considered for each
piping system used.
It is advised that the circulating pump for
each boiler be installed as close to the boiler
as possible in the line to the return connection
such that system water is pumped towards the
boiler.
Installing circulating pumps so that the water
is pumped away from the boiler is rarely
recommended.
Means to eliminate air from the boiler/piping
systems is a must. It is advised that an air
separator be installed as close as practical to
each boiler in the outlet pipe. Further, an air
vent should be installed at all high points
throughout the piping system.
It is recommended that a water meter be
installed in the make-up water system to the
boiler system. Scheduled recording of the
water meter register will show an indication of
a potential slow system leak in addition to
providing insight into any system problems.
Also, make-up water as well as water for the
initial system fill should be provided through
a water softener. Additionally, chemical
treatment of the system water is advisable.
Contact a qualified boiler water chemical
treatment company for their
recommendations. See section 3.8 for more
information.
See Appendix F for boiler water flow pressure
drop data and Appendix E for typical boiler
piping arrangements.
3.5.4.1 Water Flow Rates (Variable Primary
Pumping Systems)
Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web:
Phone: 717-239-7642 Fax: 877-501-5212 Email:
22
Variable primary pumping systems shall be
capable of delivering no less than the
minimum and no more than the maximum
specified in Table 6 and Table 7 for each
boiler connected in the system.
Minimum Flow Rate
Model
gpm
ARC1000
4
ARC1500
6
ARC2000
8
ARC2500
10
ARC3000
12
Table 6 Minimum Water Flow Rates for
Variable Primary Pumping
Maximum Flow Rate
Model
gpm
ARC1000
95
ARC1500
143
ARC2000
190
ARC2500
238
ARC3000
285
Table 7 Maximum Water Flow Rates for
Variable Primary Pumping
WARNING
Do not use Table 6 or Table 7 to size a
constant volume pump.
www.thermalsolutions.com
sales@thermalsolutions.com
Form: 2435
Revision: 8
Date: 9-19-2016
Δ P
Low Fire
Δ T
(ft)
.04
100F
.02
100F
.03
100F
.04
100F
.05
100F
Δ P
High Fire
Δ T
(ft)
12.7
20F
9.2
20F
16.3
20F
20
20F
28.7
20F