Sec 10 Ce Approval Information - Omega DP25B-S User Manual

Strain gage panel meter
Hide thumbs Also See for DP25B-S:
Table of Contents

Advertisement

CE APPROVALS INFORMATION
This product conforms to EMC 2014/30/EU (EMC directive)
Electrical Safety: 2014/35/EU (Low Voltage Directive)
Safety requirements for electrical equipment for measurement, control and laboratory.
Double Insulation
Pollution Degree 2
Dielectric withstand Test per 1 min
• Power to Input/Output:
• Power to Input/Output:
(Low Voltage dc Power Option*)
• Power to Relays Output:
• Relay 1 to Relay 2:
• Isolated Analog to Inputs:
• Analog to Inputs:
Measurement Category I
Category I are measurements performed on circuits not directly connected to the
Mains Supply (power). Maximum Line-to-Neutral working voltage is 50 Vac/dc.
This unit should not be used in Measurement Categories II, III, IV.
Transients Overvoltage Surge (1.2 / 50uS pulse)
• Input Power:
• Input Power:
(Low Voltage dc Power Option*)
• Isolated Analog:
• Input/Output Signals:
Note: *Units configured for external low power dc voltage, 10-32 Vdc (Basic Insulation)
**I/O signal and control lines require shielded cables and these cables
must be located on conductive cable trays or in conduits. Furthermore,
the length of these cables should not exceed 30 meters
Additional Information
RoHS II: The above product has been declared by the original supplier as
Compliant. The manufacturer of this item declares that the product complies with
the EEE RoHS II Directive 2011/65/EC.
Refer to the EMC and Safety installation considerations (Guidelines) of this manual
for additional information.
56
2300 Vac (3250 Vdc)
500 Vac (720 Vdc)
2300 Vac (3250 Vdc)
2300 Vac (3250 Vdc)
1000 Vac (1420 Vdc)
No Isolation
2500 V
500 V
500 V
500 V

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents